Three-Phase Power Calculator

For balanced three-phase loads such as motors, pumps and machines. Enter the voltage, the line current and the power factor to get kW, kVA and kvar, or start from a kW or kVA rating to find the current in each line. You can type the voltage between lines (400 or 415 V) or between a line and neutral (230 or 240 V).

What do you know?
The voltage you entered is

0 to 1, or a percentage. From the nameplate or a meter.

Formula: S = √3 × V(L-L) × I, P = S × PF, Q = S × sin φ. Assumes a balanced load (the same current in each line)

These are textbook formulas for learning, checking and planning. They do not size cables, fuses, breakers or earthing, and they are not a substitute for a licensed electrician. Any wiring work must follow your local electrical code.

Three-phase power in plain terms

A three-phase supply has three live lines whose voltages peak one after another, a third of a cycle apart. It is standard in factories, large buildings and many farms.

Line and phase voltage

There are two voltages to know. Between any two lines you measure the line-to-line voltage, for example 400 V or 415 V. Between a line and neutral you measure the line-to-neutral voltage, which is smaller by a factor of √3, about 1.732, giving 230 V or 240 V. This page lets you type either; choose the matching option.

The formulas used

For a balanced load, where each line carries the same current:

  • Apparent power S = √3 × line voltage × line current, in VA.
  • Real power P = S × power factor, in W.
  • Reactive power Q = S × sin φ, in var, where φ is the angle whose cosine is the power factor.

Going the other way, the current in each line is P ÷ (√3 × V × power factor), or S ÷ (√3 × V) if you start from kVA.

Worked example

A pump has a nameplate of 7.5 kW, 415 V, 0.84 power factor and 89 % efficiency. Its electrical input is 7.5 ÷ 0.89 ≈ 8.43 kW. Choose kW, type 8.43, 415 and 0.84, and the page gives about 14 A per line and roughly 10 kVA. That matches the nameplate current closely, which is a good check that the readings make sense.

Star and delta

Whether the motor windings are connected in star or delta changes the voltage across each winding, but the line formulas above stay the same as long as you use line values.

Limits

Unbalanced loads, such as several single-phase appliances spread unevenly over the lines, need a per-phase sum instead; the single-phase power calculator handles each phase. Starting currents and harmonics are not included. For sizing supply equipment, see the transformer sizing calculator.

How to use Three-Phase Power Calculator

  1. Choose what you know: volts and amps, kW, or kVA.
  2. Say whether the voltage is line to line or line to neutral, then type it.
  3. Type the current or power and the power factor, and read the results and working.

Privacy: how it works

Calculations run in your browser. The values you enter are not sent anywhere.

Frequently asked questions

Why is there a √3 in three-phase power?

In a balanced system the voltage between two lines is √3 (about 1.732) times the voltage from a line to neutral. Total power is three times one phase, which works out as √3 × line voltage × line current × power factor.

What is the current of a 15 kW motor on 415 V?

At a power factor of 0.85, 15 kW of input power is 15,000 ÷ (1.732 × 415 × 0.85) = 24.6 A. A motor rated at 15 kW output draws more because of its efficiency; the nameplate current is the figure to trust.

Does it handle unbalanced loads?

No. It assumes the same current in each line. For unbalanced loads, work out each phase with the single-phase calculator using the line-to-neutral voltage and add the results.