Power Factor Calculator
Work out a power factor from meter or nameplate readings, then see what capacitor would raise it. The correction section gives the capacitor rating in kvar, the drop in kVA and current, and, if you add the voltage and frequency, the capacitance in microfarads for single-phase or for each phase of a delta or star bank.
Work out the power factor
Formula: PF = P ÷ S = cos φ, S = √(P² + Q²).
Capacitor needed to improve the power factor
Optional: add the supply voltage to get the capacitance in microfarads.
Formula: Qc = P × (tan φ1 − tan φ2), C = Qc ÷ (2π f V²).
Capacitor banks need the right voltage rating, discharge resistors and protection, and can cause resonance with harmonics. Have an electrician or your supplier select and install them.
These are textbook formulas for learning, checking and planning. They do not size cables, fuses, breakers or earthing, and they are not a substitute for a licensed electrician. Any wiring work must follow your local electrical code.
What power factor tells you
Power factor compares the power a load really uses (kW) with the volts-times-amps the supply has to deliver (kVA). A value of 1 means every amp is doing useful work. A value of 0.7 means the cables, switchgear and transformer carry about 43 % more current than the work strictly needs.
Induction motors, welding sets, older fluorescent fittings and lightly loaded transformers all pull the figure down, because they need magnetising current that flows back and forth without doing work.
Three ways to find it
- From kW and kVA, as shown on many energy meters: PF = kW ÷ kVA.
- From kW and kvar: the apparent power is √(kW² + kvar²), then divide.
- From a voltmeter, a clamp meter and a power reading: PF = W ÷ (V × A) on single-phase, or W ÷ (√3 × V × A) on three-phase.
Keep both figures on the same scale. Mixing W with kVA gives an answer a thousand times too small.
Correcting it with capacitors
Capacitors draw current that cancels some of the reactive current of motors. The rating needed is kvar = kW × (tan φ1 − tan φ2), where φ1 and φ2 are the angles of the present and target power factors.
Example: a plant drawing 150 kW at 0.75 wants to reach 0.95. The tangents are about 0.882 and 0.329, so it needs roughly 83 kvar. Its apparent demand falls from 200 kVA to about 158 kVA, and the current falls by around 21 %.
Add the supply voltage and frequency to see the capacitance. On three-phase, the page gives it per phase for a delta bank and a star bank; delta needs a third of the star value because each capacitor sees the full line voltage.
Before buying a bank
Over-correcting at light load can push the power factor past 1 and raise the voltage. A qualified electrician should choose and fit the equipment.
How to use Power Factor Calculator
- Choose what you know and type the readings, keeping kW and kVA (or W and VA) on the same scale.
- For correction, type the load in kW, the present power factor and the target.
- Optionally add the supply voltage and frequency to get the capacitance.
Privacy: how it works
Calculations run in your browser. The values you enter are not sent anywhere.
Frequently asked questions
What is a good power factor?
Closer to 1 is better: less current for the same work, so lower cable losses and smaller kVA demand. Many supply companies set a minimum or charge for low power factor; check your own tariff for the figure.
How is the capacitor size worked out?
Capacitor kvar = kW × (tan φ1 − tan φ2), where φ1 and φ2 are the angles of the present and target power factors. 100 kW from 0.70 to 0.95 needs about 69 kvar.
Should I correct to exactly 1?
Usually not. Aiming for 1 risks over-correction when the load drops, which can raise the voltage. Most installations target a little below 1, and banks are often switched in steps.
Related tools
- Three-Phase Power Calculator
- Single-Phase Power Calculator
- Transformer Sizing Calculator
- Power Calculator (Watts)