Voltage Drop Calculator

See how many volts a cable loses over its length. Enter the current, the one-way length and the conductor resistance per kilometre (or per 1000 ft) from the cable maker's data sheet. For large AC cables you can add the reactance and power factor. Type your own percentage limit to get a pass or fail and the longest run that stays within it.

Supply

Distance from the supply to the load, not the total of both wires.

From the cable maker's data sheet, ideally the AC resistance at operating temperature.

Leave blank for small cables; matters for large cables.

Type the limit from your local code or specification. None is assumed.

Formula: Vd = 2 × I × L × (R cos φ + X sin φ). L is the one-way length; single-phase and DC count the outgoing and return conductor

Voltage drop is only one check. This page does not check whether the cable can carry the current safely (its current rating depends on how it is installed) or whether the protective device will trip in time. Those come from your local wiring code and the cable maker.

These are textbook formulas for learning, checking and planning. They do not size cables, fuses, breakers or earthing, and they are not a substitute for a licensed electrician. Any wiring work must follow your local electrical code.

Why long cables lose voltage

Every conductor has some resistance, so current flowing through it loses a little voltage along the way. Over a long run to a borewell pump, a garden building or a far corner of a factory, it can be enough to make motors run hot, lights dim and electronics reset.

What you need to type

  • The supply type and voltage. For three-phase, use the voltage between lines.
  • The load current in amps.
  • The one-way length: the distance from the board to the load, not the total wire used.
  • The conductor resistance per kilometre (the same number as milliohms per metre) or per 1,000 feet, from the cable maker’s data sheet.
  • For large AC cables, the reactance per kilometre and the load’s power factor.

The method

For DC and single-phase circuits the current goes out on one conductor and back on another, so the drop is 2 × current × length × resistance. For balanced three-phase it is √3 × current × length × resistance, measured between lines. With reactance included, the resistance term becomes R × cos φ + X × sin φ.

Example: a 230 V single-phase run of 40 m carrying 16 A on cable with 4.61 Ω/km drops about 5.9 V, or 2.6 %, leaving roughly 224 V at the load.

Limits are your input

Wiring codes set the drop allowed, and the figures differ by country and by circuit type. The page assumes none. Type the limit from your code or project specification and you get a pass or fail plus the longest run that stays within it.

What it does not check

A cable that passes on voltage drop may still be too small to carry the current safely, or may not let the fuse or breaker clear a fault quickly enough. Those checks depend on how the cable is installed and on your local rules, so have them done by a licensed electrician. To work out the load current first, use the current calculator.

How to use Voltage Drop Calculator

  1. Choose DC, single-phase or three-phase and type the supply voltage and load current.
  2. Type the one-way cable length and the conductor resistance from the data sheet.
  3. Read the drop in volts and percent, the voltage at the load and the power lost.

Privacy: how it works

Calculations run in your browser. The values you enter are not sent anywhere.

Frequently asked questions

Why do I have to type the cable resistance?

Resistance depends on the conductor size, material, temperature and how the maker builds the cable. Using the figure from your own cable's data sheet is more accurate than a generic table.

What voltage drop is allowed?

It depends on your country's wiring code and the type of circuit, so the page assumes no limit. Type the percentage from your code or specification in the limit box.

Does this tell me if the cable is big enough?

Only for voltage drop. A cable must also carry the current without overheating and let the protective device trip in time. Those checks need your wiring code and an electrician.