UPS Capacity Calculator
Choose a UPS or home inverter that can carry your load. List each device and its watts, set a power factor and some spare headroom, and the calculator gives the minimum rating in both VA and watts. Checking both numbers matters, because many UPS boxes are sold by VA but can supply fewer watts.
List everything the UPS must keep running. Use the watts on each device’s label or power adapter; a desktop PC normally draws much less than its power-supply rating, so a measured figure is better.
Editable assumption used to turn watts into VA. Change it if you know your load's power factor.
Spare capacity so the UPS does not run at its limit and you can add devices later.
Formula: UPS watts = total load × (1 + headroom ÷ 100); UPS VA = UPS watts ÷ power factor. Rounded to whole VA and watts. How long the UPS lasts on battery is a separate question: use the UPS runtime calculator.
Choosing the right UPS size
An uninterruptible power supply, or a home inverter that does the same job, has two limits printed on it: volt-amperes (VA) and watts. Shops often advertise only the VA figure, yet the watt figure is usually lower, and it is the watts that decide whether your equipment will run. Overload either limit and the unit beeps, switches to bypass or shuts down.
Listing the load
Write down everything that must keep running in a power cut: computer, monitor, router, modem, a few lights, perhaps a fan or a television. Use the watts on each label or power brick. A desktop’s power-supply rating is its maximum, not what it normally draws; a measured figure from a plug-in meter gives a more realistic total. Leave out laser printers and heaters, which draw large bursts and are best kept off a small UPS.
Power factor and VA
Real power in watts and apparent power in VA differ by the power factor. Dividing watts by the power factor gives VA. The calculator starts at 0.8 as an editable assumption. If your devices or the UPS maker give a different figure, change it.
Headroom
Running a UPS at full capacity shortens battery life and leaves no room for another device. Headroom adds a percentage on top of the load. With 500 W of equipment and 25% headroom, you need at least 625 W, which at a power factor of 0.8 is about 781 VA. Look for a model at or above both numbers.
Size versus backup time
A bigger UPS does not automatically last longer. Backup time depends on its batteries and on how much you draw from them. Once you have chosen a size, estimate hours with the UPS runtime calculator, or plan a larger battery bank with the battery sizing calculator.
Limits
Motors, pumps and compressors need far more power for a moment as they start, which many small UPS units cannot supply. Ask the seller before connecting them.
How to use UPS Capacity Calculator
- Add each device the UPS must power, with its watts and quantity.
- Keep or change the power factor and the headroom percentage.
- Pick a UPS whose VA and watt ratings are both at least the figures shown.
Privacy: how it works
Calculations run in your browser. The figures you enter are not sent anywhere.
Frequently asked questions
What is the difference between VA and watts?
Watts are the real power your devices use. VA (volt-amperes) is volts × amps, which is higher when the load’s power factor is below 1. VA = watts ÷ power factor.
Why add headroom?
A UPS running at its limit gets hot, gives less backup time and cannot take one more device. Headroom keeps a margin; you can set it to 0 if you prefer.
Does this tell me how long the UPS will last?
No. Size and backup time are separate. Backup time depends on the batteries; use the UPS runtime calculator for that.