Electrical Load Calculator
Work out how much load you are connecting before you apply for a new connection, a load increase or a backup system. List each load with its watts and quantity, choose single-phase or three-phase and your supply voltage, and set how much runs at the same time. You get the connected load, maximum demand in kW and kVA, and the current in amps.
Your supply voltage as stated by your electricity company.
Share of the connected load you expect to run at the same time. 100% = everything on together.
Editable assumption. 1 for heaters and filament lamps; lower for motors and electronics.
Formula: connected load = Σ watts × quantity; maximum demand = connected × demand factor. kVA = kW ÷ power factor. Current: single-phase I = W ÷ (V × PF); three-phase I = W ÷ (√3 × V × PF), using the line-to-line voltage and assuming a balanced load. This is an estimate for planning or for asking your electricity company for a sanctioned load; cable and breaker sizes must follow your local wiring rules and be chosen by a qualified electrician.
Connected load and maximum demand
When you ask for a new supply or a higher sanctioned load, the electricity company usually wants a list of what you will connect. Adding the rated watts of every light, fan, socket appliance, pump and machine gives the connected load. In practice not everything runs at once, so engineers also estimate the maximum demand: the highest load expected at a single moment.
The demand factor
The demand factor is the share of the connected load you expect to run together. At 100% you assume everything is on. A home with two water heaters, an oven and an air conditioner may rarely run all four at the same time, so a lower figure can be reasonable, but the choice is yours and depends on how the building is used. Some suppliers and wiring codes publish their own factors; if yours does, use them.
From kilowatts to kVA and amps
Equipment with motors or electronic power supplies draws current that is not perfectly in step with the voltage. The power factor describes this. Apparent power in kVA equals real power in kW divided by the power factor, and the current follows from it. On a single-phase supply, amps = watts ÷ (volts × power factor). On three phases, divide by √3 × the line-to-line voltage × power factor, which assumes the load is spread evenly over the phases.
Example
Three 1,000 W heaters and two 500 W pumps make 4 kW connected. At a 75% demand factor the maximum demand is 3 kW. With a power factor of 0.9 that is 3.33 kVA, and on a 230 V single-phase supply about 14.5 A.
What this does not do
It does not pick cables, breakers or earthing. Those depend on cable type, run length, grouping, ambient temperature and the wiring regulations where you live, and a qualified electrician must design and test the installation. Use the figures to plan, compare options or prepare your application, and to size backup with the generator sizing calculator.
How to use Electrical Load Calculator
- Add each load with its power in watts and how many there are.
- Choose single-phase or three-phase and type your supply voltage.
- Set the demand factor and power factor, then read the connected load, maximum demand and current.
Privacy: how it works
Calculations run in your browser. The figures you enter are not sent anywhere.
Frequently asked questions
What is the difference between connected load and maximum demand?
Connected load is everything added together. Maximum demand is what you expect to run at the same moment, found by multiplying by a demand factor. At 100% the two are the same.
How is the current worked out?
Single-phase: amps = watts ÷ (volts × power factor). Three-phase: amps = watts ÷ (√3 × line voltage × power factor), assuming the load is shared evenly across the phases.
Can I choose a cable or breaker from the result?
No. Cable and breaker sizes depend on the installation method, length, temperature and your local wiring rules. Give these figures to a qualified electrician.
Related tools
- Energy Consumption Calculator
- Generator Sizing Calculator
- UPS Capacity Calculator
- Electricity Bill Calculator